The all-weather dehumidifier is widely used in ship, pharmaceutical and other related industries. It is often used to reduce humidity and temperature in special coating operation cabinet, thus ensuring workers comfortable working environment. It works by both treating air and recreating air. The core of the design is a high-efficient dehumidifying wheel, whose huge surface area ensures its ability to absorb plenty of vapor.
Model | SSCE-DU12025-AC |
Name | Combined air conditioner |
Power | 3Phase ; 380V±10% ; 50Hz |
Main Contorl System | 100% Refrigeration / Refrigeration + 100%reheating |
Static Pressure | 3000 Pa |
Process Airflow | 12000 m3/Hr |
Compressor Power | CSH6553-50-38P/117.7kw |
Refrigeration Compressor Power | 1×38kw |
Blower Power | 1×15kw |
Condenser | 2×4kw |
Reheating Capacity | Front 72kw ;Back 42kw, divided into three gears |
Power Consumption | 173kw |
Refrigerant | R22 |
Reheating | Electric heater, stainless steel |
Temperature Control Method | Highly sensitive temperature probe |
Discharge Dimension | 6×φ250mm |
Environmental Conditions | <45℃/ RH 40%~95% |
Discharge Condition | 25±2℃ / RH≤40% |
Evaporator | Copper Tube+Aluminium Fans(Evaporation area: 260㎡) |
Condenser | Copper Tube+Aluminium Fans (Condensation area 623㎡) |
Condensation Form | Air cooled |
Case Construction | Frame + insulation box |
Control Interface | PLC+ Touch screen control |
Control Box | IP54 IP54 sealing / leakage / fault phase / low voltage + overload protection |
Temperature Control | Display of ambient temperature, outlet temperature, evaporator temperature, etc |
Electricity Flow Display | Each group of motors and heaters has an ammeter to display the load |
Pressure Display | High and low pressure and hydraulic differential display + high and low pressure protection |
Fault Display | After heating over temperature, evaporator overcooling, power failure, preheating over temperature, ambient temperature overrun, etc. |
Air filter | Washable iron frame double layer filter |
Weight | 4000Kg,based on the weight of the final equipment |
External Dimension | 3000(L)×2000(W)×2550(H) based on the dimension of the final equipment |
![]() | ![]() | ![]() |